Salgenx

Roof Mounted Array Energy Storage


Salgenx Grid Scale Saltwater Battery
Salgenx Saltwater Battery: A revolutionary energy storage solution for grid-scale and sustainable power needs. With non-toxic, eco-friendly saltwater electrolytes, Salgenx offers high efficiency, durability, and safety for renewable energy integration. Ideal for large-scale storage, data centers, and off-grid systems.



Publication Title | Roof Mounted Array Energy Storage

Grid Scale Storage Publications Search

Search Tesla Megapack Publications search was updated real-time via Filemaker on:

Search Tesla Megapack Publications | Return to Search List

Search Completed | Title | Roof Mounted Array Energy Storage
Original File Name Searched: 2022-03-28_March_28_2022_1150_San_Roque.pdf | Google It | Yahoo | Bing


Previous Page | Next Page
roof-mounted-array-energy-storage-001</TD> <TD valign=

Page | 001

HGFEDCBA
AC ADA
BLDG CLR CONC COMM DC DIA DIST EQ EGC
(E) EA. EMT ESS EV GAB GALV GEC
GND HVAC
I
IMP INV ISC KVA KW KWH LV MAX MIN
ALTERNATING CURRENT AMERICANS WITH DISABILITIES ACT
BUILDING
CLEAR
CONCRETE
COMMUNICATION
DIRECT CURRENT
DIAMETER
DISTANCE
EQUAL
EQUIPMENT GROUNDING CONDUCTOR
EXISTING
EACH
ELECTRICAL METALLIC TUBING
ENERGY STORAGE SYSTEM ELECTRIC VEHICLE GRADED AGGREGATE BASE GALVANIZED
GROUNDING ELECTRODE CONDUCTOR
GROUND
HEATING, VENTILATION, & AIR CONDITIONING
CURRENT
CURRENT AT MAX POWER INVERTER
SHORT CIRCUIT CURRENT KILOVOLT AMPERE KILOWATT KILOWATT-HOUR LOW-VOLTAGE
MAXIMUM
MINIMUM
MV (N) NEC NIC NRTL
NTS OC PCC PL PLC PV
PP PVC RSD SCH SQ. IN. SS SSD STC
TYP UON VIF W
MEDIUM-VOLTAGE
NEW
NATIONAL ELECTRIC CODE NOT IN CONTRACT NATIONALLY-RECOGNIZED TESTING LABORATORY NOT TO SCALE
ON CENTER
POINT OF COMMON COUPLING PROPERTY LINES
POWER LINE COMMUNICATION PHOTOVOLTAIC
POWERPACK
POLYVINYL CHLORIDE
RAPID SHUTDOWN
SCHEDULE
SQUARE INCHES
STAINLESS STEEL
SEE STRUCTURAL DRAWINGS STANDARD TESTING CONDITIONS
TYPICAL
UNLESS OTHERWISE NOTED VERIFY IN FIELD
WATT
VICINITY MAP
PROJECT DESIGNER:
KYLE PECEVICH
TESLA, INC.
2562 BLVD. OF THE GENERALS, STE 200 NORRISTOWN, PA 19403
860-924-7015 KPECEVICH@TESLA.COM
STRUCTURAL ENGINEER OF RECORD: KIRILL VORONOV
TESLA, INC.
721 FERNCREST RD
TRINIDAD, CA 95570 P:(818) 943-7621 KVORONOV@TESLA.COM
ELECTRICAL ENGINEER OF RECORD: ALEX SHORTS
TESLA, INC.
10430 SHADY TRAIL #108 DALLAS, TX, 75220 P:(805) 663-3812 ASHORTS@TESLA.COM
PROJECT MANAGER:
TOPHER BLUNT
TESLA, INC.
3500 DEER CREEK RD. PALO ALTO, CA 94304
P: (805) 798-1094 CBLUNT@TESLA.COM
TESLA - 901 PAGE ROOF-MOUNTED PV ARRAY
APN: 055-171-007
1. WIND DESIGN
- DESIGN WIND SPEED = 92 MPH
(ULTIMATE)
- RISK CATEGORY = II
2. WIND EXPOSURE = C 3. SEISMIC DESIGN
- RISK CATEGORY = II
- SEISMIC IMPORTANCE FACTOR = 1.0
- S_S = 2.163 g, S_1 = 0.781 g
- SITE CLASS = D
- S_DS = 1.73 g, S_D1 = 0.885 g
- SEISMIC DESIGN CATEGORY = E
- BASIC SEISMIC-FORCE-RESISTING
SYSTEM = NON-STRUCTURAL
COMPONENT
- R = 2.5 / a_p = 1.0
NOMINAL POWER
PEAK APPARENT POWER
ENERGY RATING
SYSTEM TOTALS
BATTERY (LITHIUM)
280 kVA
490 kVA
1392 kWh
AERIAL MAP
PROJECT LOCATION
N WE
S
INSTALLATION OF ENERGY STORAGE SYSTEM.
NEW CONCRETE SLAB WITH TESLA ENERGY STORAGE EQUIPMENT.
TREE TO BE REMOVED ON SITE.
FENCELINE TO BE RELOCATION AROUND NEW EQUIPMENT.
BOLLARDS TO BE INSTALLED FOR EQUIPMENT PROTECTION.
THE SUBJECT PARCEL HAS A SMALL AREA WITHIN THE FEMA SPECIAL
FLOOD HAZARD AREA (SFHA) FLOODPLAIN. NO FLOOD MITIGATION MEASURES ARE REQUIRED FOR THE PROPOSED STRUCTURE SINCE IT IS NOT WITHIN THE FLOODPLAIN BOUNDARY.
(N) PROJECT LOCATION
(E) UTILITY METER
ABBREVIATIONS
PROJECT TEAM
DESIGN CRITERIA
SYSTEM SUMMARY
PROJECT DATA
PROJECT SCOPE
SHEET #
G-001
E-101
E-111
SHEET INDEX
N WE
S
ENERGY STORAGE SYSTEM (ESS)
APN: 055-171-007
ZONE: RS-1A
LOT SIZE: 12.22 ACRE SLOPE: 21%
HIGH FIRE: YES
FLOOD ZONE: YES (AE,X)
SHEET TITLE
G-002
COVER PAGE
NOTES
ELECTRICAL SITE PLAN
EQUIPMENT PLAN
E-112
DETAILED EQUIPMENT PLAN
POWERPACK TYPE
PART #
QTY
DISCHARGE
MANUFACTURER
PART #
QUANTITY
INVERTER 1
2.0
1490027-00-A
8
4.97 HR
1
E-113
E-200
E-201
E-211
L-101
S-101
EQUIPMENT ELEVATION
EQUIPMENT SCHEDULE
SINGLE LINE DIAGRAM
COMMUNICATION DIAGRAM
TESLA
1134768-G2-A
E-241
E-601
E-701
ELECTRICAL DETIALS
CUTSHEETS
LABELS & PLACARDS
LANDSCAPE PLAN
STRUCTURAL SITE PLAN
APPLICABLE CODES
NFPA 70-2017
S-102
S-501
DETAILED SITE PLAN
STRUCTURAL DETAILS
IBC 2018
2019 CBC/ASCE 7-16
2019 CFC
2019 CEC
REFERENCED DOCUMENTS
POWERPACK SYSTEM INSTALLATION MANUAL
MICROGRID ISLANDING CONTROL SPECIFICATION
3500 DEER CREEK RD. PALO ALTO, CA 94304 (650) 681-5000
ORIGINAL SIZE 24"X36" SHEET SIZE ARCH "D"
0 12" 1"
PROFESSIONAL STAMP
TESLA - 901 PAGE
ROOF-MOUNTED PV ARRAY
TESLA
901 PAGE AVE
FREMONT, CA 94538
DATE
10/26/21
REVISION
AHJ COMMENTS
NO.
A
6
5
4
3
2
1
COVER PAGE
G-001
JB-94538924
REV: B IFP
PLOT DATE: 12/10/2021 5:00 PM
KPECEVICH
REFERENCED DOCUMENTS
PROPRIETARY AND CONFIDENTIAL

Search Contact: greg@salgenx.com